Product Introduction
After years of research and development, our company has successfully developed a series of high-intelligence, high-precision battery discharge testers using our proprietary technology.
The discharge tester can operate in offline mode, using the battery as the discharge load. By continuously regulating the discharge current, it maintains a constant discharge current at the set value. During discharging, the instrument will automatically stop when any of the following conditions is met: the battery terminal voltage or individual cell voltage falls to the preset lower limit, the set discharge time is reached, or the set discharge capacity is achieved. Throughout the process, all valuable and continuous real-time data is recorded.
The battery discharge tester system uses wireless relay access to collect voltage monitoring information from individual cells in a simple, safe, and accurate manner.
The tester features a highly user-friendly interface, allowing users to complete various settings and data queries under menu prompts. Discharge process data can be saved in the device's internal memory and transferred to a USB drive via the data interface. The data can then be analyzed using dedicated PC software to generate required curves and reports.
The battery discharge tester is equipped with comprehensive protection functions, including audible and visual warnings, as well as clear on-screen interface prompts to ensure safe operation.
Parâmetros técnicos
| Modo de trabalho | pode ser usado sozinho, pode ser usado simultaneamente, pode ser controle remoto e monitoramento de status | ||||
| Applicable battery | 48 V | 110V | 220 V | 380 V | other electrical test groups can be customized |
| Tensão de descarga | 0~60V | 88~132V | 176V~275V | 300V~456V | |
| Corrente de descarga | 0~150A | 0~100A | 0~100A | 0~30A | |
| Precisão da corrente | 1% | ||||
| Precisão de tensão | 0.5% | ||||
| Precisão da tensão do monômero | 0.2% | ||||
| Tensão de monômero | 0.500V~16.00V(resolution 1mv) | ||||
| Tempo de descarga de carga | 0 ~ 99 horas e 59 minutos | ||||
| Fonte de energia | CA:220V | ||||
| Maneira de resfriamento | resfriamento de ar forçado | ||||
| Packaging | aluminum alloy pull box | ||||
Ambiente de trabalho
| Dissipação de calor | resfriamento de ar forçado |
| Temperatura | working range: -5 ~ 50℃ storage temperature: -40 ~ 70℃ |
| Umidade | relative to humidity0 ~ 90% (40±2℃) |
| Altitude | altitude nominal: 4000 m |
| Barulho | ﹤60dB |
Fonte de alimentação de trabalho
| Tensão | sistema monofásico de três fios: 220 V CA (- 20% ~ + 30%), frequência: 45 ~ 65 Hz |
| Teste de tensão suportável | entrada - caixa: 2200V DC 1min |
| entrada-saída: 2200V DC 1min | |
| saída - caixa: 700V DC 1min | |
| Segurança | atender EN610950 |
Fiação
| Entrada CA | Gb socket, suitable for 1 ~ 1.5mm2cabo |
| Saída CC | instrument 25 mm2Cable quick connect plug (red positive black negative) |
Product Characteristics
Constant Current Discharge Function: Continuously adjustable current enables accurate battery capacity measurement.
Wireless Cell Voltage Monitoring: Each wireless monitoring module can simultaneously monitor up to 12 individual cells.
PC Analysis Software with Remote Control: Includes Chinese-language background analysis software and supports remote-controlled discharge functionality.
Data Interface & Storage: The host is equipped with a USB interface and 2GB of high-capacity internal data storage.
Dual CPU Operation: Dual processors work together to ensure test safety, reliability, and accuracy.
Flexible Discharge Control: Discharge can be paused and parameters modified without terminating the discharge test.
after-sale service