qiao@hvtest.cc15871365102
  • Transformador de teste de descarga parcial sem imersão em óleo da série YDJW

    A impedância de tensão é melhor do que o padrão nacional, e a impedância do sistema não ultrapassa 5%. Design inovador, tamanho compacto e leveza. Adotando tecnologia de controle automático, o grau de automação e a capacidade anti-interferência foram aprimorados.

    Product Details of YDJW Series Oil Immersed No Partial Discharge Test Transformer

    Product Introduction:

    Oil immersed non partial discharge test transformer refers to a test transformer with no or very small partial discharge capacity, suitable for conducting partial discharge tests and power frequency withstand voltage tests on various electrical equipment, electrical components, and insulation materials.


    Product functions:

    High-voltage output: Provides a stable and reliable high-voltage test power source.

    Low partial discharge: The equipment itself has a low partial discharge level, reducing background interference during testing.

    Power-frequency withstand voltage testing: Meets the power-frequency withstand voltage testing requirements of various high-voltage electrical equipment.

    Partial discharge testing: Provides high-voltage excitation for insulation performance and partial discharge detection of electrical equipment.

    Insulation performance testing: Used to evaluate the insulation performance of transformers, cables, GIS, and other equipment.


    Technical parameters:

    Parâmetro

    Preço

    Capacidade nominal

    50-1200kVA

    Tensão de entrada

    380 V

    Voltagem de saída

    50-1200kV

    Run time

    ≤ 5 minutes

    Precisão de medição

    ≤1.5%

    Partial discharge capacity

    ≤5Pc

    Protection function

    Overcurrent and voltage protection alarm automatically return to zero


    Product Features:

    1. Adopting an oil type epoxy cylinder structure, it has small partial discharge, low loss, light weight, and low waveform distortion.

    2. Low impedance voltage, superior to national standards.

    3. Multi layer shielding, strong anti-interference ability.

    4. High insulation level, local discharge capacity ≤ 5pc.

    5. Equipped with automatic protection device, over-current and over-voltage protection, and high reliability performance.


    Application Scenarios

    Power transformer testing: Used for partial discharge and power-frequency withstand voltage testing of transformers.

    GIS and high-voltage switchgear testing: Used for insulation performance testing of GIS, switchgear, circuit breakers, and other equipment.

    High-voltage cable testing: Used for withstand voltage and partial discharge testing of high-voltage cables, joints, and terminations.

    CT/PT/CVT testing: Used for insulation performance and withstand voltage testing of instrument transformers.

    High-voltage bushing and insulator testing: Used for withstand voltage and partial discharge detection of high-voltage insulation components.

    Insulating material testing: Used for high-voltage performance testing of various electrical insulating materials.

    Research and laboratory testing: Used for high-voltage insulation research in universities, research institutions, and enterprise laboratories.

    Electrical equipment factory testing: Used for factory, type, and quality testing of various high-voltage electrical equipment.


    FAQs

    Q1: What is this oil-immersed partial discharge-free test transformer mainly used for?

    A1: This equipment is mainly used for power-frequency withstand voltage testing and partial discharge testing of various high-voltage electrical equipment. It provides a stable high-voltage test power source for transformers, GIS, switchgear, cables, instrument transformers, bushings, insulators, and other insulating materials.

    Q2: What electrical products can this equipment test?

    A2: The equipment is suitable for insulation performance testing of various high-voltage electrical products, including power transformers, instrument transformers, high-voltage cables and accessories, GIS, switchgear, circuit breakers, high-voltage bushings, and insulators. It can also be used for related high-voltage testing of insulating materials.

    Q3: Why choose a partial discharge-free test transformer?

    A3: During partial discharge testing, partial discharge generated by the test equipment itself may become background interference. The low partial discharge design reduces the equipment's own interference, helping to improve the ability to detect weak partial discharge signals from the product under test.








    Você pode gostar também

    • Tem alguma pergunta!

      NÃO HESITE EM ENTRAR EM CONTATO CONOSCO A QUALQUER MOMENTO
      Contate-nos
    • Visite-Nos

      Edifício 6, Parque Industrial Óptico-Mecânico Optics Valley, 84 Gaoxin 5 Road,
      Zona de Desenvolvimento de Nova Tecnologia de East Lake, cidade de Wuhan, província de Hubei, China

    • Envia-nos um email

      qiao@hvtest.cc

    • Ligue para nós

      +86-15871365102